• Direct installation into exhaust gas duct
• Media temperature from +150 to +600 °C
• Re-calibration in ambient air
• Remote sensor
• Linearized analog output 4-20 mA or 0-10 V
• RS485 Modbus RTU interface for direct Fieldbus networking

E2606L-O2 stationary oxygen analyzer is designed to measure
oxygen content in exhaust gases in oil-, gas-, wood chip-, pellet-,
coal and other biofuel fired boilers and furnaces.
The analyzer uses solid state electrochemical zirconium dioxide
sensor, providing high measurement accuracy and long-term
stability in the wide range of gas temperature. E2606L-O2 with a
controller and actuator allows to optimize the ratio of air / fuel
consumption, increasing the boiler efficiency.
The oxygen analyzer consists of two parts: the oxygen sensor
probe with 2 m cable and the transmitter unit. E2606L-O2 is
designed for industrial use.
The linear analog output 4-20 mA or 0-10 V corresponds to the
oxygen concentration and the deviation is less than 1% O2 for the
range 2-21% O2. The analog output enables to connect the
analyzer to a logger or a controller for monitoring or control the
burning process. A digital RS485 interface with Modbus RTU
protocol allows direct Fieldbus networking of up to 31 units. The
relay output can be used to set an alarm or to adjust the burning
process by appropriate actuator.

Specifications
Measuring range:                      2…21 % vol O2
Gas media temperature range: +150…+600 °C
Accuracy:                                   ± 1% vol O2
Stability:                                    ± 0.5% vol O2 after 2000 hours
Temperature effect:                   < 0.001% vol O2 per 1 degree C
Response time:                          t90 <40 s
Warm-up time:                           approx. 15 min
Exhaust gas speed:                   5 m/s max.
Sensor lifetime:                           > 10 000 hours (1 year) @ gas media temperature 300 °C
Analog output:                           4-20 mA or 0-10 V, linearized, output scale 0-25% vol O2
Digital interface:                         RS485, Modbus RTU protocol, - up to 31 addressable
                                                   instruments in RS485 Fieldbus network
Relay switching contacts:           230 V, 2 A
Power supply:                            13... 15 VDC ± 5% (2 A), power consumption 30 VA max
Transmitter enclosure:               - grey ABS plastic, 80×120×58 mm, protection class IP54
Operating conditions:                -10...+60 °C, 5...95 %R H
Sensor:                                      - M18x1,5 threaded connection, 2 m cable
 
 
 