Universāls kontrolieris ar 2-ām ieejām ATR171
Pievienot
pieprasījumu sarakstam
pieprasījumu sarakstam
Four versions are available with different hardware resources: Outputs configurable as relays (also as Open/Close logic for motorized valves control), SSR, 4…20mA, 0…10Volt signal (both for command or re-scalable retransmission of process/setpoint). The switching power supply with extended range 24…230Vac/Vdc does not require any jumpers setting. Control modes: On/Off, PID+Autotuning, Heating/Cooling PID with neutral zone.
Software features include the launch of Tuning, the selection of 2-4 setpoints by digital input, the optional manual reset of output by frontal keyboard (“Limit controller”), and the Timer function for working time (useful to simplify systems that feature two different devices for regulation and timer functions).
Most complete model is provided with two analog inputs featuring “EASYUP” modality for sensors self-configuration (for example: RH96 model Humidity + Temperature), or for the remote - setpoint from another Master device(controller/PLC). Double loop version allows also to make average or difference between the analog inputs to extract the setpoint control and is provided with serial communication RS485 with ModbusRTU protocol.
SIZE: 72x72(frontal) x 99mm(depht)
POWER SUPPLY: 24…230 Vac / Vdc +/- 15% 50/60Hz
POWER CONSUMPTION: 5W
DISPLAY: dual green/red, 4 digits, 8 red LED, decimal point
OPERATING CONDITIONS: 0-45°C, 35..95rH%
INPUTS:
1 selectable for TC K, J, S, R, PT100 (2 scales), NI100, PT1000, PT500, PTC1K, NTC10K
0…10V, 0…40mV, 0/4…20mA (also for remote setpoint), Pot. 6KΩ, Pot. 150KΩ.
1 (only ATR171-23ABC-T) selectable for TC K, J, S, R, PT100 (2 scale), NI100, PT1000, PT500, PTC1K, NTC10K
OUTPUTS
ATR171-11ABC : 1 relay 8A resistive, 1 SSR output
ATR171-12ABC : 2 relay 8A resistive, 1 SSR output
ATR171-14ABC : 3 relay 8A resistive, 1 relay 5A/30V
ATR171-23ABC-T : 3 relay 8A resistive, 1 output SSR/mA/Volt (command or retransmission, galvanic isolated from supply and sensor input) + RS485 Modbus
DIGITAL INPUT: Tuning start, multi-setpoint selection, Man/Auto, Lock Display, Start/Stop cycle (not on -23ABC-T)
CONTROL: ON/OFF, P, PI, PID Autotuning
ACCURACY: 0.5%±1digit for TC/RTD; 0.2%±1digit for V/mA
SAMPLING TIME: selectable (max 15ms)
SEALING: IP54 Frontal (IP65 with gasket), IP30 Box, IP20 Terminal blocks
CONFIGURATION: Parameters protected by password, Memory card with battery, software LabSoftView for quick setting and storage of parameters on PC
EASYUP setting options: Temperature/humidity/pressure sensors, retransmission output, remote control
← atpakaļ